IS 456:2000

Nominal concrete cover for durability and fire resistance

Determines the nominal cover to reinforcement from exposure condition (Table 16), fire resistance (Table 16A) and the member-specific minimums for columns and footings.

References:cl. 8.2.2.1 & Table 3Table 5cl. 26.4Table 16Table 16A
Design is adequateGoverning: (cl. Table 5)
100%max. utilisation
Report details
Nominal cover cnomc_{nom}
30 mm
Durability cover cdurc_{dur}
30 mm
Fire cover cfirec_{fire}
20 mm
Max. free w/c ratio w/cw/c
0.50
Min. cement content
300 kg/m³

Design checks 1

CheckClauseDemandLimitUtilisation
Table 525.0 MPa25.0 MPa100%OK

Detailed calculation

Durability — Table 16

1
cdur=30 mm(Moderate exposure)c_{dur} = 30\ \mathrm{mm}\quad (\text{Moderate exposure})
Table 16

Fire resistance — Table 16A

1
cfire=20 mm(1 h)c_{fire} = 20\ \mathrm{mm}\quad (1\ \text{h})
Table 16A

Member-specific requirements

2
cϕ=ϕ=20 mmc_{\phi} = \phi = 20\ \mathrm{mm}
26.4.1

Nominal cover not to be less than the bar diameter.

Nominal cover

1
cnom=max⁡(cdur, cfire, cmember, ϕ)=max⁡(30, 20, 0, 20)=30 mmc_{nom} = \max(c_{dur},\,c_{fire},\,c_{member},\,\phi) = \max(30,\,20,\,0,\,20) = \mathbf{30}\ \mathrm{mm}
✓ OK · 100%InputsResults

Scope, assumptions and limitations

  • Covers are nominal covers to all steel including links (cl. 26.4.1). Actual cover should not deviate from the nominal cover by +10 mm / 0 mm (Table 16, Note 2).
  • Fire covers apply to the main reinforcement; check minimum member dimensions to IS 456 Fig. 1 separately.