Nominal concrete cover for durability and fire resistance
Determines the nominal cover to reinforcement from exposure condition (Table 16), fire resistance (Table 16A) and the member-specific minimums for columns and footings.
References:cl. 8.2.2.1 & Table 3Table 5cl. 26.4Table 16Table 16A
IndianCodeApplied — calculation report
| Calculation | Nominal concrete cover for durability and fire resistance |
|---|---|
| Project | — |
| Engineer | — |
| Reference | — |
| Date |
Inputs
| Member type | Beam |
|---|---|
| Support condition | Simply supported |
| Largest bar diameter | 20 mm |
| Exposure condition | Moderate |
| Concrete grade | M25 |
| Fire resistance | 1 h |
Design is adequateGoverning: (cl. Table 5)
100%max. utilisation
Nominal cover
30 mm
Durability cover
30 mm
Fire cover
20 mm
Max. free w/c ratio
0.50
Min. cement content
300 kg/m³
Design checks 1
| Check | Clause | Demand | Limit | Utilisation |
|---|---|---|---|---|
| Table 5 | 25.0 MPa | 25.0 MPa | 100%OK |
Detailed calculation
Durability — Table 16
1
Table 16
Fire resistance — Table 16A
1
Table 16A
Member-specific requirements
2
26.4.1
Nominal cover not to be less than the bar diameter.
Nominal cover
1
Scope, assumptions and limitations
- Covers are nominal covers to all steel including links (cl. 26.4.1). Actual cover should not deviate from the nominal cover by +10 mm / 0 mm (Table 16, Note 2).
- Fire covers apply to the main reinforcement; check minimum member dimensions to IS 456 Fig. 1 separately.