Durability and corrosion assessment

Half-cell potential (corrosion probability)

Maps the electrochemical potential of reinforcement to locate areas where corrosion is likely to be active.

Standards:ASTM C876

Equipment

  • Copper/copper sulphate (CSE) reference electrode
  • High-impedance digital voltmeter (≥ 10 MΩ)
  • Connecting leads and clamp for the reinforcement
  • Sponge and wetting solution
  • Cover meter, drill

Procedure

  1. Locate the reinforcement with a cover meter; expose a bar and check electrical continuity across the test area.
  2. Connect the voltmeter positive terminal to the reinforcement and the negative to the electrode.
  3. Pre-wet the surface, then take readings on a grid (typically 0.5–1.0 m spacing) with the electrode on a wet sponge.
  4. Plot equipotential contours of the readings.

Results and acceptance criteria

  • More positive than −200 mV (CSE): greater than 90% probability of no corrosion.
  • −200 to −350 mV: corrosion activity uncertain.
  • More negative than −350 mV: greater than 90% probability of active corrosion.
  • Readings are influenced by moisture, coatings and carbonation; confirm with breakouts.

This page summarises the procedure for site and laboratory use. Follow the current edition of the cited standards (with amendments) and the project specification, which govern.