Flexural strength (modulus of rupture)
Tensile strength in bending — used for pavements (PQC), and to check fcr assumptions.
Standards:IS 516 (Part 1/Sec 1):2021IRC 44 / IRC 58 (pavements)
Equipment
- Beam moulds 150 × 150 × 700 mm (or 100 × 100 × 500 mm for aggregate ≤ 19 mm)
- Flexural testing frame with two supporting rollers and two loading rollers (third-point loading)
- Testing machine
Procedure
- Cast and cure beams as for cubes; test wet immediately after removal from water.
- Place the beam on rollers at a span of 600 mm (400 mm for 100 mm beams) with the cast face vertical.
- Apply load through two rollers at the third points without shock, increasing continuously at the rate given in IS 516 (Part 1/Sec 1) (historically 400 kg/min for 150 mm beams and 180 kg/min for 100 mm beams), until failure.
- Measure the distance a between the line of fracture and the nearer support, on the tension face.
Calculation
fracture within the middle third (a > 200 mm for 150 mm beams)
fracture outside the middle third, 170 mm < a < 200 mm; discard if a < 170 mm
Results and acceptance criteria
- IS 456 cl. 6.2.2 estimates flexural strength as 0.7√fck (e.g. 3.5 MPa for M25).
- Pavement quality concrete is usually specified directly by flexural strength (e.g. 4.5 MPa at 28 days).
This page summarises the procedure for site and laboratory use. Follow the current edition of the cited standards (with amendments) and the project specification, which govern.