Hardened concrete — strength tests

Core test (in-situ strength)

Determines the strength of concrete actually in the structure when cube results fail, are missing, or when assessing existing buildings.

Standards:IS 516 (Part 4):2018 — sampling, preparing and testing coresIS 456 cl. 17.4 — assessment and acceptance
Evaluate your results → Core test evaluation: Converts core crushing loads to core strength, corrects for length/diameter ratio, converts to equivalent cube strength and checks the IS 456 acceptance criterion (average ≥ 85% and each core ≥ 75% of the specified cube strength).

Equipment

  • Core drilling machine with diamond-tipped core barrel (water-cooled), anchoring kit
  • Cover meter / rebar locator to avoid reinforcement
  • Core cutting saw, capping set (sulphur mortar or grinding)
  • Compression testing machine
  • Vernier caliper

Procedure

  1. Locate reinforcement with a cover meter and mark core positions clear of bars; avoid zones of high stress and member edges.
  2. Drill cores perpendicular to the surface with a diameter of at least 3 times the maximum aggregate size (100 mm or 150 mm preferred); aim for a length/diameter ratio of 2 (not less than 1 after trimming).
  3. Inspect and photograph the core (voids, honeycombing, embedded steel). Cores with reinforcement parallel to the axis should be rejected.
  4. Trim and cap the ends square, measure dimensions, and soak in water for 48 hours before testing (or test as specified).
  5. Load at a steady rate until failure and record the maximum load. Repair the core holes with non-shrink grout.

Calculation

fcore=Pπd2/4f_{core} = \dfrac{P}{\pi d^2/4}
Correction for l/d: k=0.11 n+0.78,  n=l/d (1≤n≤2)\text{Correction for } l/d:\ k = 0.11\,n + 0.78,\ \ n = l/d\ (1 \le n \le 2)
fcube,eq=1.25 k fcoref_{cube,eq} = 1.25\,k\,f_{core}

Results and acceptance criteria

  • IS 456 cl. 17.4.3: the concrete represented is acceptable if the average equivalent cube strength of the cores is at least 85% of the cube strength of the specified grade at that age and no individual core is below 75%.

This page summarises the procedure for site and laboratory use. Follow the current edition of the cited standards (with amendments) and the project specification, which govern.