Structural assessment

Load test on a structure or member

Proves the strength and stiffness of a slab, beam or floor when concrete quality or construction is in doubt and other tests are inconclusive.

Standards:IS 456 cl. 17.6
Evaluate your results → Load test evaluation: Works out the test load (full dead load plus 1.25 × imposed load) and evaluates the measured deflections against the IS 456 criteria

Equipment

  • Test load: sand bags, water tanks or calibrated weights
  • Dial gauges or LVDTs (0.01 mm) on an independent reference frame
  • Props for safety under the member
  • Thermometer, data sheet

Procedure

  1. Load test should be carried out not earlier than 28 days after casting; install safety props with a small gap below the member.
  2. Take initial deflection readings, then apply a load equal to the full dead load plus 1.25 times the imposed load (allowing for the self-weight already acting), in increments.
  3. Keep the load in place for 24 hours and record the maximum deflection.
  4. Remove the imposed load and record the deflection 24 hours after removal to obtain the recovery.

Calculation

Δlim=40 l2D  (mm; l in m, D in mm),Recovery=Δmax−ΔresΔmax\Delta_{lim} = \dfrac{40\,l^2}{D}\ \ (\mathrm{mm};\ l\ \text{in m},\ D\ \text{in mm}),\qquad \text{Recovery} = \dfrac{\Delta_{max} - \Delta_{res}}{\Delta_{max}}

Results and acceptance criteria

  • If the maximum deflection during the 24 hours under load is less than 40 l²/D, recovery need not be measured (IS 456 cl. 17.6(b)).
  • Otherwise the structure should recover at least 75% of the deflection within 24 hours of removal of the load. If not, the test may be repeated after 72 hours; if recovery is then less than 80% the structure is deemed unacceptable.

This page summarises the procedure for site and laboratory use. Follow the current edition of the cited standards (with amendments) and the project specification, which govern.