Cover meter / rebar locator
Locates reinforcement and measures concrete cover — for durability checks, and to plan cores and fixings.
Standards:BS 1881-204 (method)IS 456 cl. 26.4 and Table 16 (required cover)
Equipment
- Electromagnetic (eddy-current) cover meter with search probe
- Calibration block
- Marker and grid template
Procedure
- Calibrate the meter for the bar diameter expected.
- Scan the surface slowly in two perpendicular directions; mark bar positions where the signal peaks.
- Read the cover directly above each bar; use the diameter-estimation mode if the bar size is unknown and confirm with a small breakout where critical.
Results and acceptance criteria
- Compare measured cover with the nominal cover of IS 456 Table 16 (permitted deviation +10 / 0 mm).
- Readings are affected by closely spaced or layered bars; verify by breakout at a few points.
This page summarises the procedure for site and laboratory use. Follow the current edition of the cited standards (with amendments) and the project specification, which govern.