IS 1893 (Part 1):2016

Seismic base shear and storey forces — equivalent static method

Design horizontal seismic coefficient Ah, approximate natural period, design base shear VB with the minimum base shear check, and the vertical distribution of lateral forces and storey shears for regular buildings.

References:cl. 6.4.2cl. 6.4.3cl. 7.2.1cl. 7.2.2cl. 7.3cl. 7.6.1cl. 7.6.2cl. 7.6.3Table 3Table 6Table 7Table 8Table 9
Report details
Design acceleration coefficient AhA_h
0.0378
Natural period TaT_a
0.864 s
Seismic weight WW
35300 kN
Design base shear VBV_B
1334.2 kN
Base shear / weight
3.78 %
Storey shear distribution
0200400600800100012001400051015202530Storey shear (kN)Height (m)
  • Vi
  • Qi
Lateral forces and storey shears
Floorhi (m)Wi (kN)Wi hi² (kN·m²)Qi (kN)Storey shear Vi (kN)
8 (roof)26.0038002568800366.7366.7
722.8045002339280333.9700.6
619.6045001728720246.8947.3
516.4045001210320172.81120.1
413.204500784080111.91232.0
310.00450045000064.21296.2
26.80450020808029.71325.9
13.604500583208.31334.2

Detailed calculation

Seismic parameters

5
Z=0.24 (Zone IV),I=1,R=5Z = 0.24\ (\text{Zone IV}),\quad I = 1,\quad R = 5
Table 3, 8, 9
h=3.60+(8−1)×3.20=26.00 mh = 3.60 + (8 - 1) \times 3.20 = 26.00\ \mathrm{m}
Ta=0.075 h0.75=0.864 sT_a = 0.075\,h^{0.75} = 0.864\ \mathrm{s}
7.6.2
Sag=1.575(Type II — medium stiff soil)\dfrac{S_a}{g} = 1.575\quad (\text{Type II — medium stiff soil})
6.4.2
Ah=Z2 IR Sag=0.242×15×1.575=0.03780A_h = \dfrac{Z}{2}\,\dfrac{I}{R}\,\dfrac{S_a}{g} = \dfrac{0.24}{2} \times \dfrac{1}{5} \times 1.575 = 0.03780
6.4.2

Seismic weight and base shear

4
W=∑Wi=35300 kNW = \sum W_i = 35300\ \mathrm{kN}
7.4
VB=Ah W=0.03780×35300=1334.2 kNV_B = A_h\,W = 0.03780 \times 35300 = 1334.2\ \mathrm{kN}
7.6.1
VB,min=ρˉ W=1.6%×35300=564.8 kNV_{B,min} = \bar{\rho}\,W = 1.6\% \times 35300 = 564.8\ \mathrm{kN}
7.2.2, Table 7
VB=1334.2 kNV_B = 1334.2\ \mathrm{kN}

Vertical distribution

1
Qi=VB Wi hi2∑j=1nWj hj2,∑Wjhj2=9347600 kN m2Q_i = V_B\,\dfrac{W_i\,h_i^2}{\sum_{j=1}^{n} W_j\,h_j^2},\quad \sum W_j h_j^2 = 9347600\ \mathrm{kN\,m^{2}}
7.6.3

Scope, assumptions and limitations

  • Dynamic analysis is required (cl. 7.7.1) for regular buildings of height ≥ 15 m in Zones III–V or ≥ 40 m in Zone II, and for irregular buildings > 12 m in Zones IV–V or > 40 m in Zones II–III. Dynamic results are scaled up to the VB computed here (cl. 7.7.3).
  • Seismic zone factors are per the 2016 zone map; check the latest amendment of IS 1893 for revised zonation of your site.